2.2.3 Portrait Orientation
Note: Follow Rack-Mount Gasket Installation procedure (if necessary) prior to beginning
the steps below.
1. Align mounting plate rack-mount holes with server rack mounting holes; see
Figure 4 for correct mounting orientation. Ensure gasket faces outward.
2. Install the eight 10-32 1/2 button head bolts into rack-mounting holes to secure
mounting plate to the server rack.
Note: Steps 3 & 4 require two people.
3. Align studs with the monitor mounting holes in mounting plate and install the
CYRAQ
®
until the gasket is flush with rear of enclosure.
Important!
Do not exceed 30 in/lbs when tightening mounting nuts.
4. From inside rack, a second person must install and tighten the fourteen 10-32
mounting nuts.
Figure 4: Rack-Mount Portrait Installation