[UPS->Bank Control] Display the current state of each outlet Bank, and it provides on/off control for the
Non-Critical Outlet Bank. Outlet Number and Device Name displays the device name associated with
the specific outlet.
Item
Definition
Bank Control Options
ON
Turns non-critical bank on immediately.
OFF
Turns non-critical bank off immediately.
Device Name Identification
Outlet #
UPS outlet number as designated by the outlet configuration (varies by
UPS model).
Device Name
Device Name assigned to this outlet.
[UPS->Diagnostics] The UPS/Diagnostics page provides the ability to verify UPS batteries are in
adequate working conditions. You can also complete a runtime calibration to insure an accurate
estimation for the connected load.
Battery Test
The Battery Test will force the UPS to switch to battery power for 10 seconds. This allows the user to
verify the battery conditions and provides information about the battery, including the results and date of
the last battery test. Click the “Start” button to begin a battery test.
The following information will be reported after a battery test completes.
• Last Test Date: The date of the most recent battery test.
• Last Test Result: The results of the most recent battery test.
Passed: The battery performed normally during the test.
Failed: The battery test did not pass.
Follow the steps below if the battery test fails:
Repeat the battery test and replace the batteries if the test fails again.
Contact CyberPower for assistance if the battery test fails after the batteries have been
replaced.
Note: “N/A” means the UPS model does not have the battery test function.
Runtime Calibration
The Runtime Calibration ensures the runtime estimate is accurate with the load and the current battery
capacity. The results show the Estimated Runtime, Last Elapsed Runtime, Last Calibration Result, and
Last Calibration Date.
When a runtime calibration is initiated, the UPS will run on battery power until the batteries are
completely discharged. The UPS will then automatically switch to input power. The batteries will start to
recharge upon the completion of the calibration.