CyberPower Remote Management System
11
enable the UPS to function normally. If this option is selected, the
UPS will be forbidden to enter Bypass mode or ECO mode to protect
the connected equipment.
ECO Mode
On-line UPS enters Economy mode. The UPS will enter Bypass
mode when the input voltage/frequency is within the configured
threshold. Once the utility voltage/frequency exceeds thresholds, the
UPS will switch to Normal operation.
Manual Bypass
Determines whether to allow the UPS to enter Manual Bypass mode.
If this option is enabled, the UPS will be forced to enter Bypass
mode.
Bypass
Note: The UPS may automatically enter Bypass Mode per these
configured settings.
Bypass Condition
No Bypass: If this option is selected, the UPS will not enter Bypass
mode and will stop supplying output power.
Check Volt/Freq: If the utility voltage is in the range of the voltage
thresholds and the utility frequency is in range of the frequency
tolerance, the UPS will enter Bypass mode. Otherwise the UPS will
stop supplying output power.
Check Volt Only: Only if the utility voltage is in the range of the
voltage thresholds, the UPS will enter Bypass mode. Otherwise the
UPS will stop supplying output power.
Bypass When UPS Off
When the UPS turn off, the UPS switch to Bypass Mode.
Power Restore
After utility power is restored, the UPS turns on automatically and
supplies power to the connected equipment. The following settings
are used to configure the UPS restore behavior:
Automatic Restore
When this option is enabled, the UPS will restore output immediately
when the utility power restores. When this option is disabled, the
UPS will not restore output at that moment and users have to turn it
on manually at a later time.
Recharged Delay
When utility power restores, the UPS will start to recharge until the
specified delay is expired before restoring output power.
Recharged Capacity
When utility power restores, the UPS will start to recharge until the
specified battery capacity is met before restoring output power.
Returned Delay
The Returned Delay will take effect every time when the UPS is
turned on. This also includes the scheduling and user controlling
task.
Line Stable Delay
When the UPS is in battery mode and utility power restored, the UPS
would wait for the specific delay time to change battery mode to line
mode. When the UPS battery is already lower then Low Battery
Threshold and utility power restored, the UPS would return to line
mode immediately.