Make sure that there is no other application utilizing port 3052 (UDP/TCP) and port 53568 (TCP). Use a
command prompt with the command netstat -o to obtain information about which ports are used by which
programs.
Ensure the PowerPanel
®
Business Edition service is running on the hosted computer. If the service is
stopped, restart the service and then try again in the same way.
Make sure the port 3052 (UDP/TCP) and port 53568 (TCP) on the hosted computer are not blocked by a
firewall.
Make sure the URL in the address filed of the browser for a remote computer is correct.
2. I have installed the PowerPanel
®
Business Edition Agent on my computer, but the Agent cannot establish
communication with the UPS.
Make sure that no other application is using the serial port if the UPS is connected with a serial cable.
Make sure the serial or USB cable is securely and properly connected to the UPS and computer.
3. The Client cannot establish communication with the UPS/PDU/ATS.
The lack of communication may be caused by the following conditions:
The network communication between the Client computer and the UPS/PDU/ATS is down.
The device network address is configured improperly.
The authentication settings are configured improperly.
Follow the steps below to resolve the problem:
Verify the device network address is correct.
Verify the network configuration in the device is correct. Use the Power Device Network Utility tool to
configure the device network configuration.
Verify the settings on the Security/Authentication page are correct and match the settings of the
UPS/PDU/ATS. See Security/Authentication for more details.
Verify the port on the Security/Network page is matched if establishing communication with Agent.
Check the network status of the UPS/PDU/ATS and Clients.
Verify firewall settings. Port 3052(UDP/TCP), port 53568(TCP), port 161(UDP), port 162(UDP) and port
53566(UDP) should be unblocked. The Client communicates with UPS/PDU/ATS and Agents using these
ports.
4. The battery test failed.
Replace the batteries if the batteries have used over 3 years.
Contact CyberPower for assistance and replace the batteries if the battery test still fails.
5. The PowerPanel
®
Business Edition installation failed.
If the installation file is from CyberPower web site, it may have downloaded incompletely or become corrupt.
Download the installation file again.