Specifications
19
cpsww.com
The LCD display panel provides critical
load and battery information.
LINE-INTERACTIVE
PR750LCDRM1U / PR1000LCDRM1U
PR2200LCDRT2U
Rack/Tower UPS Specifications 750VA – 3000VA
Pure Sine Wave Models Input Output General
Model
Capacity
(VA /
Watts)
Runtime
Half/Full
Load
(Min)
Voltage
Range
(VAC)
Frequency
Range
(Hz)
NEMA
Plug
Type
NEMA
Outlet
Type
(Qty)
On
Battery
Voltage
(VAC)
On
Battery
Frequency
(Hz)
Comm.
Ports
Cord
Length
(ft)
Rack
Size
Energy
Saving
Compatible
Extended Battery
Module
PR750LCDRM1U
750/
560
23/7 80–150 50–60±3 5-15P (6) 5-15R 120 ±5%
50/60
± 0.1%
HID USB,
Serial, SNMP,
EPO
10 1U
a
N/A
PR1000LCDRM1U
1000/
750
14/ 5 80 –150 50–60±3 5-15P (6) 5-15R 120 ±5%
50/60
± 0.1%
HID USB,
Serial, SNMP,
EPO
10 1U
a
N/A
PR1000LCDRT2U 3
1000/
700
32/11 80 –150 50–60±3 5-15P (8) 5-15R 120 ±5%
50/60
± 0.1%
HID USB,
Serial, SNMP,
EPO
10 2U
a
N/A
PR1500LCDRT2U 3
1500 /
1000
18/6 80–150 50–60±3 5-15P (8) 5-15R 120 ±5%
50/60
± 0.1%
HID USB,
Serial, SNMP,
EPO
10 2U
a
N/A
PR2200LCDRT2U 3
2170 /
1600
16/6 80–150 50–60±3 5-20P (8) 5-15/20R 120 ±5%
50/60
± 0.1%
HID USB,
Serial, SNMP,
EPO
10 2U
a
N/A
PR3000LCDRT2U 3
3000/
2250
8/3 80–150 50–60±3 L5-30P
(8) 5-20R
(1) L5-30R
120 ±5%
50/60
± 0.1%
HID USB,
Serial, SNMP,
EPO
10 2U
a
BP48V75ART2U3
3TAA compliant model available.
2U
1U
A
B
C
D
D
E
E
F
G
H
A
Multifunction LCD
B
Power Safety Cover
C
Select Button
D
Noncritical Load Outlets
E
Critical Load Outlets
F
SNMP Slot
G
USB Port
H
EPO Port
I
RG6 Coax Protection
J
RJ11/45 Protection
K
Serial Port
L
Output Breaker
M
Input Breaker
N
Cooling Fan
J
I
H
F
G
K
K
L
L
M
M
N
N
K