Specifications

12
1.877.297.6 937
SMART APP SERIES
OL8000TF / OL10000TF
E
C
D
A
B
Tower UPS with Step-Down Transformer Specifications 6kVA – 10kVA
Pure Sine Wave Models Input Output General
Model
Capacity
(VA /
Watts)
Runtime
Half/Full
Load
(Min)
Voltage
Range
(VAC)
Frequency
Range
(Hz)
NEMA
Plug
Type
NEMA
Outlet
Type
(Qty)
On
Battery
Voltage
(VAC)
On
Battery
Frequency
(Hz)
Comm.
Ports
Cord
Length
(ft)
UPS/Transformer
Dimensions
WxHxD (in)
Energy
Saving
Compatible
Extended
Battery Module
OL6000TF
6000/
5400
15.8/5.3 200 240 40–70 HW
5-20R (12)
L6-20R (4)
L6-30R (6)
120 and
200, 208,
220, 230,
240
50/60
±0.25%
HID USB
Serial
SNMP
EPO
N/A
10.4 x 23.6 x 26/
10.4 x 18.2 x 16.9
a
BP240V30A
OL8000TF
8000/
7200
13/5 200 240 40–70 HW
50/60
±0.25%
N/A
10.4 x 23.6 x 26/
10.4 x 18.2 x 16.9
a
BP240V50A
OL10000TF
10000/
9000
11/4 200 240 40–70 HW
50/60
±0.25%
N/A
10.4 x 23.6 x 26/
10.4 x 18.2 x 16.9
a
BP240V50A
Extended Battery Module Visit website for added runtimes.
Model UPS Compatibility Recharge Time Voltage
Battery
(Qty)
Dimensions
WxHxD (in)
Weight (lbs) Warranty
BP240V30A
OL6000TF 4 Hours 240V 12V / 7. 2A H ( 20 ) 10.4 x 23.6 x 26 16 7. 2 3 Years
BP240V50A
OL8000TF, OL10000TF 5 Hours 240V 12V/9AH (20 ) 10.4 x 23.6 x 26 167. 2 3 Years
23.6”
18.2
A
EPO Port
D
Relay Output
B
SNMP Slot
E
Serial, USB, Remote LCD Ports
C
Back-Feed Protection
F
High Volume Fan
G
Input Breaker
H
Output Breaker
I
Noncritical Load Outlets
J
RJ45 Protection
K
Extended Battery Port
N
Hard-Wired AC Input
L
Critical Load Outlets
O
Hard-Wired AC Output
M
Hard-Wired AC Bypass
P
Steel Caster
Q
Leveling Feet
Q
P
O
N
N
M
L
K
J
J
I
I
H
H
H
H
H
H
H
H
G
F
F