User Manual

DEFINITIONS FOR ILLUMINATED LCD INDICATORS
TROUBLESHOOTING
1 . INPUT voltage meter: This meter measures the AC voltage that the UPS system
is receiving from the utility wall outlet. The UPS is designed, through the use of
automatic voltage regulation, to continuously correct output voltage to connected
equipment to a safe 110/120 voltage output range. In the event of a complete power
loss, severe brownout, or over-voltage, the UPS relies on its internal battery to
supply consistent 110/120 output voltage. The INPUT voltage meter can be used as a
diagnostic tool to identify poor-quality input power.
2 . OUTPUT voltage meter: This meter measures, in real time, the AC voltage that the
UPS system is providing to the connected devices, such as normal line mode, AVR
mode, and battery backup mode. (Note: The OUTPUT voltage meter shows the status
of the battery backup outlets.)
3 . ESTIMATED RUN TIME: This displays the run time estimate of the UPS with current
battery capacity and load.
4 . NORMAL icon: This icon appears when the UPS is working under normal conditions.
5 . BATTERY icon: During a severe brownout or blackout, this icon appears and an alarm
sounds (two short beeps followed by a pause) to indicate the UPS is operating from
its internal batteries. During a prolonged brownout or blackout, the alarm will sound
continuously to indicate the UPS’s batteries are nearly out of power. You should
save files and turn off your equipment immediately or allow the software to shut the
system down.
6 . AVR (Automatic Voltage Regulation) icon: This icon appears whenever your UPS is
automatically correcting low AC line voltage without using battery power. This is a
normal, automatic operation of your UPS, and no action is required on your part.
7 . SILENT MODE icon: This icon appears whenever the UPS is in silent mode. The buzzer
does not beep during silent mode until the battery reaches low capacity.
8 . OVER LOAD icon: This icon appears and an alarm sounds to indicate the battery-
supplied outlets are overloaded. To clear the overload, unplug some of your
equipment from the battery-supplied outlets until the icon turns off and the alarm
stops.
9 . FAULT: This icon appears if there is a problem with the UPS. Press the POWER button
to turn the UPS off.
E01 : Charger Fault-Overcharge (Contact CyberPower Systems for support.)
E02: Charger Fault-No Charge (Contact CyberPower Systems for support.)
E11: Battery Overvoltage (Contact CyberPower Systems for support.)
E21: Output Short (Check the status of equipment connected to the UPS and then
turn on the UPS again.)
E22: Overload (Unplug at least one piece of equipment from battery outlets and turn
the UPS on again.)
10
. BATT. CAPACITY meter: This meter displays the approximate charge level (in 20%
increments) of the UPS’s internal battery. During a blackout or severe brownout, the
UPS switches to battery power, the BATTERY icon appears, and the charge level
decreases.
11 . LOAD CAPACITY meter: This meter displays the approximate output load level (in
20% increments) of the UPS battery outlets.
For more information about functions setup, please refer to the Function Setup Guide.
Problem Possible Cause Solution
Circuit breaker button is projecting from the back of
the unit.
Circuit breaker has tripped due to an overload.
Turn the UPS off and unplug at least one piece of equipment.
Wait 10 seconds, reset the circuit breaker by depressing the
button, and then turn the UPS on.
The UPS does not perform expected runtime.
Battery not fully charged. Recharge the battery by leaving the UPS plugged in.
Battery is worn out.
Please contact CyberPower Systems about replacement
batteries.
The UPS will not turn on.
The on/off switch is designed to prevent damage from
rapidly turning it off and on.
Turn the UPS off. Wait 10 seconds and then turn the UPS on.
The unit is not connected to an AC outlet. The unit must be connected to a 120V 60Hz outlet.
The battery is worn out. Please contact CyberPower Systems.
Mechanical problem. Please contact CyberPower Systems.
PowerPanel® Personal
is inactive (all icons are gray).
The USB cable is not connected.
Connect the USB cable to the UPS unit and an open USB port
on the back of the computer. You must use the cable that came
with the unit.
The USB cable is connected to the wrong port.
Check the back of the computer for an additional USB port.
Move the cable to this port.
The unit is not providing battery power.
Shutdown your computer and turn the UPS off. Wait 10 seconds
and turn the UPS back on. This should reset the unit.
The USB power ports are not providing power to the
connected devices.
The USB power port has Over Current Protection design.
When the total current of connected devices is over
specification
,
the USB power ports will stop providing power
to the connected devices.
Turn the UPS off and unplug at least one piece of device
connected to the USB power port and then turn the UPS on.
Additional troubleshooting information can be found under “Support” at www.cyberpowersystems.com
TECHNICAL SPECIFICATIONS
Model
CST135UC CST150UC
Capacity 1350VA / 810W 1500VA/900W
Nominal Input Voltage 120V
Input Frequency 60 Hz ± 3 Hz
On-Battery Output Voltage 120Vac ± 5%
Max. Load for UPS Outlets (5 Outlets) 1350VA / 810W 1500VA/900W
Max. Load for Full-Time Surge Protection
outlets (10 Outlets)
12 Amp
On-Battery Output Wave Form Simulated Sine Wave
Operating Temperature + 32°F to 104° F / 0° C to 40° C
Operating Relative Humidity 0 to 95% non-condensing
Size (W x H x D) 3.9" x 9.8" x 13.7" (99 x 249 x 348 mm)
Net Weight 23.59lbs / 10.7kg 25lbs/11.3kg
Battery Type CyberPower / RB1270X2C CyberPower / RB1290X2
Typical Battery Recharge Time 8 hours to 90% capacity from total discharge
Typical Battery Life 3 to 6 years, depending on number of discharge/recharge cycles
Recommended Battery Sealed Maintenance Free Lead Acid Battery
Safety Approvals UL1778(UPS), CSA C22.2 No. 107, FCC/DoC Class B
SYSTEM FUNCTIONAL BLOCK DIAGRAM
Input Output
EMI Fllter
Surge
Suppressor
AVR
Charger
AC / DC
Battery Inverter
Normal Mode
Battery Mode
This device complies with part 15 of the FCC rules. Operation is subject to the
following two conditions: (1) this device may not cause harmful interference,
and (2) this device must accept any interference received, including
interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user
is encouraged to try to correct the interference by one or more of the following measures:
FCC COMPLIANCE STATEMENT
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
Advanced Energy-Saving Patented Bypass Technology
CyberPower’s patented GreenPower UPS™ with Bypass Technology
reduces UPS energy costs by up to 75% compared to conventional UPS
models. Even when utility power is normal, conventional UPS models
constantly pass power through a transformer. By contrast, under normal
conditions the advanced circuitry of a GreenPower UPS™ bypasses the
transformer. As a result, the power efficiency is significantly increased
while decreasing waste heat, using less energy, and reducing energy costs.
When an abnormal power condition occurs, the GreenPower UPS™ automatically runs power
through its transformer to regulate voltage and provide “safe” power. Since utility power is
normal over 88% of the time, the GreenPower UPS™ operates primarily in its efficient bypass
mode.
The GreenPower UPS™ is also manufactured in accordance with the Restriction on
Hazardous Substances (RoHS) directive making it one of the most environmentally-friendly
on the market today.
G
REEN
POWER UPS
Energy-Saving Technology
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment to an outlet on a circuit different from that to which the receiver is
connected.
- Consult the dealer or an experienced radio/TV technician for help"
Warning: Changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
Canadian Compliance Statement
CAN ICES-3 (B)/NMB-3(B)
FCC COMPLIANCE STATEMENT - Continued
LIMITED WARRANTY AND CONNECTED EQUIPMENT GUARANTEE
Please visit www.CyberPowerSystems.com for a copy of the Limited Warranty and
Connected Equipment Guarantee.
Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the International Sale of
Goods is expressly excluded. CyberPower is the warrantor under this Limited Warranty.
For further information please feel free to contact CyberPower at:
Cyber Power Systems (USA), Inc.
4241 12th Ave E., STE 400, Shakopee, MN 55379;
Call us at (877) 297-6937;
or submit a web ticket online at cyberpowersystems.com/support.
WARNING: This product can expose you to chemicals including bisphenol A (BPA) and
styrene, which is known to the State of California to cause reproductive harm and cancer.
For more information, go to www.P65Warnings.ca.gov.
CyberPowerSystems.com
© 2021 Cyber Power Systems (USA), Inc.
PowerPanel® Personal is a trademark of
Cyber Power Systems (USA) Inc.
All rights reserved. All other trademarks are the property of their respective owners.
3
7
11
10
1
984 5 6
2
The LCD display indicates a variety of UPS operational conditions. All descriptions apply
when the UPS is plugged into an AC outlet and turned on or when the UPS is on battery.