User`s manual
4
Copyright © 2008 CyberPower Systems, Inc.
Refer to the battery connection diagram:
1. Connect the battery pack’s output cord into the UPS’s input port.
2. All battery pack module must connect in right type, red to red, black to black, green to
green.
3. When connecting with numerous battery packs to extend the battery runtime, link the
output plugs of all except the one that connects to the UPS.
CAUTION! Before connecting to the UPS, make sure to turn off the circuit breaker.
CAUTION! Do not disconnect the battery pack when UPS is operating.
CAUTION! Do not connect the battery pack into itself.
CAUTION! Additional battery packs are to be connected in parallel connected, the voltage
maintains the same, yet the battery amp-hour capacity depends on the numbers of battery
packs in the set up.
CAUTION! Do not connect more than the upper limit of the battery packs to the UPS. (The
battery packs limits are stated in the user’s manual.)
Battery Connection to UPS
How to set the number of battery packs connected to the UPS?
The UPS must be equipped with the appropriate number of external battery packs. In order to
recognize the battery packs, there are two ways to set up the UPS:
PowerPanel
®
Business Edition.
Press the display toggle to set up the correct battery pack numbers.
Battery Runtime Table
Model / Watts
Half load
(350W)
Full load
(700W)
50W 100W
200W
300W
400W 500W 600W
Number
of
battery
packs
Internal
32 mins
11 mins
3hrs
46mins
2hrs
6mins
58mins
36mins
26mins
18mins
14mins
+1
2hrs
11mins
50mins
11hrs
21mins
6hrs
54mins
4hrs
17mins
2hrs
36mins
1hr
46mins
1hr
24mins
1hr
7mins
+2
3hrs
56mins
1 hr
35mins
22hrs
11mins
12hrs
26mins
6hrs
44mins
4hrs
36mins
3hrs
16mins
2hrs
22mins
2hrs
2mins
+3
5hrs
47mins
2hrs
21mins
33hrs
1min
18hrs
10hrs
01mins
6hrs
34mins
5hrs
3hrs
50mins
3hrs
2mins
+4
7hrs
38mins
3hrs
08mins
43hrs
51mins
23hrs
34mins
12hrs
45mins
8hrs
55mins
6hrs
20mins
5hrs
1min
4hrs
8mins
Trouble Shooting
Problem Possible Cause Solution
The UPS LCD does
not perform expected
runtime.
Do not set the UPS to
recognize the battery
pack(s).
By pressing the display toggle to select
functions. Then, set up the correct
battery pack numbers. The default
setting is 0.
The battery pack
does not work.
Batteries are not fully
charged.
Allow the battery pack to charge for 24
hours. Do not expect full runtime during
this initial charge period.
Specified battery pack models can use
AC to shorten charge time.
The status of circuit
breaker is off.
Switch on the circuit breaker.
The fuse blew.
Contact CyberPower Systems.
Open the cover on the rear panel and
replace a new fuse.