“Advanced Options” menu. For each virtual device, select a tape device emulation
for backup hosts to see and use.
Receive SNMP messages from UPS
This menu option allows you to enable the HSTC to receive SNMP messages
from an APC® Smart-UPS® model UPS that has a Network Management Card or
a Tripp Lite® SmartPro®/SmartOnline™ model UPS that has an 
SNMPWEBCARD. You can configure the UPS to send messages to the HSTC
when the power fails, enabling the HSTC to automatically shut itself down cleanly.
By enabling this option, you allow the miSAN-V-Series to take the following
actions in response to the UPS power events:
Event Action
AC power failed; UPS on battery The  miSAN-V-Series  remains  operational
but prepared for shutting down quickly.
AC power restored before UPS battery is drainedThe  miSAN-V-Series  returns  to
normal operation.
UPS battery is low The  miSAN-V-Series  shuts  down  cleanly,
ensuring the safety of saved data.
Configuring an APC® Smart-UPS® model UPS with Network Management Card
You must configure the Network Management Card’s network parameters so the
Smart-UPS can communicate with the miSAN-V-Series. Under “Network” >
“SNMP”, set “Access” to “Enabled”. Under “Events” > “Recipients > “Trap Receiv-
ers”, enter the following information:
Community Name
public
Receiver NMS IP/Domain Name [IP address of miSAN-V-Series]
Generation
Enabled
Authentication Traps Disabled
Note 
Device emulation may require a driver to be installed on the host 
computer system.
Caution 
The miSAN-V-Series does not authenticate the UPS, so enabling this 
option enables anyone capable of sending SNMP messages on your 
network to shut down the miSAN remotely. 