User manual
P. 8
< 1.6 > IP Multi-port connection to remote PDU
LINK OUT
RESET
ON DIP
1876
5
432
CURRENT
(
A
)
225
To Multi port
CyberView Matrix IP KVM
Other band IP KVM can NOT connect InfraPower PDU
To LINK port
of the 1st PDU
CAT. 5 / 6
cable
Up to 20 meters
LINK OUT
RESET
ON DIP
1876
5
432
CURRENT
(
A
)
225
LINK OUT
RESET
ON DIP
1876
5
432
CURRENT
(
A
)
225
CAT. 5 / 6
cable
Up to 20 meters
To LINK port
of next PDU
( Up to 16 levels )
1st level PDU 3rd level PDU2nd level PDU
2468
10121416
1357
9111315
18202224
26283032
17192123
25272931
Using the dip switch no. 1, 2, 3, 4 & 8
to setup each PDU level acording to the table :
Cascaded PDUs Dip switch no.
12348
1st PDU On On On On Off
2nd PDU Off On On On Off
3rd PDU On Off On On Off
4th PDU Off Off On On Off
5th PDU On On Off On Off
6th PDU Off On Off On Off
7th PDU On Off Off On Off
8th PDU Off Off Off On Off
9th PDU On On On Off Off
10th PDU Off On On Off Off
11th PDU On Off On Off Off
12th PDU Off Off On Off Off
13th PDU On On Off Off Off
14th PDU Off On Off Off Off
15th PDU On Off Off Off Off
16th PDU Off Off Off Off Off
Dip switch setting
ON DIP
76
5
432
18
ON DIP
76
5
432
18
ON DIP
76
5
432
18
Each RJ-45 Multi port connect max. 16 pcs of InfraPower PDU
CyberView IP KVM provides RJ-45 Multi port for the user to remotely control and manage servers & PDU together.