Function LCD Display Options Default Description
MAX O/P Voltage H136V ~ H142V
Escape to
Function
Menu
H139V In Utility Power settings, only 3
types of fixed voltage ranges can
be chosen. However, you can fine
tune the MAX O/P voltage in this
function.
If the utility voltage is usually high,
and the connected equipment can
work in this condition, you can set
the output voltage range higher to
reduce the UPS from going to
Battery Mode as often.
MIN O/P Voltage L97V ~ L103V
Escape to
Function
Menu
L100V In Utility Power settings, only 3
types of voltage ranges can be
chosen. However, you can fine
tune the MIN O/P voltage in this
function.
If the utility voltage is usually low,
and the connected equipment can
work in this condition, you can set
the output voltage range lower to
reduce the UPS from going to AVR
Mode or Battery Mode as often.
Audible Alarm b On
b OFF
Escape to
Function
Menu
b On If b OFF is selected, the unit will
mute all alarms except for fault or
overload condition.
Function LCD Display Options Default Description
Return to Default Settings
YES
Escape to
Function
Menu
No Action Select Yes and press the DISPLAY
Button for approximately 3 seconds
to restore the UPS factory default
settings and go back to the Status
Display.
Return to Status Display
-- Press the DISPLAY Button for
approximately 3 seconds to go
back to the Status Display.