Technical data
Safety Instructions and Warranty Terms 46
Manual econ sens+ Version 1.40
econ sens+ measuring coils:
Default settings
Network
By default the econ sens+ searches for a DHCP server; if there is no DCHP server in the network, the
following applies:
IP address: 192.168.0.1
Subnet mask: 255.255.255.0
Standard gateway 192.168.0.254
Date/Time settings
Time / Date: Adopt time and date from time server
Power settings
Network topology: Three-phase 4-wire power system (230/400V, 50 Hz)
Pulse weighting
Pulse weighting [Wh/pulse]: 10 Wh/pulse = 100 pulses/kWh
User name: user
Password: pass
Coil 170
Coil 250
Coil 350
mechanical
Overall length of coils
[mm]
170
250
350
Max.diameter of measured cable
[mm]
35
65
95
Max. bending radius
[mm]
35
Length of connecting cable
[m]
2
electrical
Measurement range
[A
rms
]
0...400
0...1600
0..3200
Resolution
[A
rms
]
0.1
Rel. error
%
+/- 1