Technical data

Safety Instructions and Warranty Terms 32
Manual econ sens+ Version 1.40
Modbus register address ranges
Range
Contents
Data size & type
2…110
Measurements - Present value
32 bit, Float
120…126
Measurements - Present value
32 bit, Float
200...216
Event flags
1 bit
300...340
Event settings
32 bit, Integer
400...406
System
16 bit, Integer
500...510
Event values
32 bit, Float
1002...1110
Measurements - Present value
32 bit, Float, gedreht
1120...1126
Measurements - Present value
32 bit, Float, gedreht
1300…1340
Event settings
32 bit, Integer, gedreht
1500…1510
Event values
32 bit, Integer, gedreht
The following is a list of all the measurement registers that can be read through modbus. All data is
expressed in floating point and uses 2 registers for 4 bytes in total. The data is available from registers
2..110 and 1002..1110. The values in both ranges are the same, but the order of the registers is
switched.
- Big-Endian (High-Byte vor Low-Byte) - Register 2…110
- Little-Endian (Low-Byte vor High-Byte) - Register 1002...1110
Modbus supports the commands “Read Holding Registers(0x03) and Read Input Registers” (0x04).
Registers 2..110 are addressed as 1..109. Only requests with a odd register address and a quantity of
registers that is a multiple of 2 are valid. Other request will return an Illegal Data Address (0x02)
exception code.
Name
Register
Description
Phase
Units
Ptot
2
Real Energy (Actual count)
L1,L2,L3
kWh
P L1
4
Real Energy (Actual count)
L1
kWh
P L2
6
Real Energy (Actual count)
L2
kWh
P L3
8
Real Energy (Actual count)
L3
kWh
Qtot
10
Reactive Energy (Actual count)
L1,L2,L3
kvarh
Q L1
12
Reactive Energy (Actual count)
L1
kvarh
Q L2
14
Reactive Energy (Actual count)
L2
kvarh
Q L3
16
Reactive Energy (Actual count)
L3
kvarh
u(L1)
18
Voltage (Present value)
L1-L2
V
u(L2)
20
Voltage (Present value)
L2-L3
V
u(L3)
22
Voltage (Present value)
L3-L1
V
un(L1)
24
Voltage (Present value)
L1-N
V
un(L2)
26
Voltage (Present value)
L2-N
V
un(L3)
28
Voltage (Present value)
L3-N
V
i(L1)
30
Current (Present value)
L1
A
i(L2)
32
Current (Present value)
L2
A