Specifications
Curtis PMC 1223/33, 1225/35, 1227/37 Manual
56
To access the Special Program mode, first press the MORE INFO key. Then,
while continuing to hold the MORE INFO key, press the PROGRAM key. The LED
on the PROGRAM key will light, just as when the programmer is in Program
mode. To distinguish between the Program and Special Program modes, look at
the menu items in the display.
CONTROLLER CLONING
Two of the Special Program Menu items—“Save Controller
Settings in Programmer” and “Load Programmer Settings
into Controller”—allow you to “clone” controllers. To do
this, simply program one controller to the desired settings,
save these settings in the programmer, and then load them
into other similar (same model number) controllers, thus
creating a family of controllers with identical settings.
The MORE INFO key is used initially to access the Special Program mode, and once
you are within the Special Program mode, it is used to perform the desired tasks.
To adjust the contrast in the display window, for example, select “Contrast
Adjustment” by scrolling until this item is at the top of the screen, and then
press MORE INFO to find out how to make the adjustment.
The Special Program Menu is presented at the end of this section.
In the Special Diagnostics mode, the controller’s diagnostic history file is
displayed. This file includes a list of all faults observed and recorded by the
controller since the history was last cleared. (NOTE: The maximum and minimum
temperatures recorded by the controller are included in the Test Menu.) Each fault
is listed in the diagnostic history file only once, regardless of the number of times
it occurred.
To access Special Diagnostics, first press the MORE INFO key. Then, while
continuing to hold the MORE INFO key, press the DIAGNOSTICS key. The LED on
the DIAGNOSTICS key will light, just as when the programmer is in Diagnostics
mode.
The MORE INFO key, when used within the Special Diagnostics mode, causes
additional information to be displayed about the selected item.
To clear the diagnostic history file, put the programmer into the Special
Program mode, select “Clear Diagnostic History,” and press the MORE INFO key
for instructions. Clearing the diagnostic history file also resets the maximum/
minimum temperatures in the Test Menu.
6 — PROGRAMMER OPERATION
DIAGNOSTICSMORE INFO
*










