Technical data

To connect PCM600 to the IED, two basic variants must be considered.
Direct point-to-point link between PCM600 and the IED front port.
Indirect link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enable
communication.
The communication procedures are the same in both cases.
1. If needed, set the IP address for the IEDs.
2. Set up the PC or workstation for a direct link (point-to-point), or
3. Connect the PC or workstation to the LAN/WAN network.
4. Configure the IED IP addresses in the PCM600 project for each IED to match the
IP addresses of the physical IEDs.
Setting up IP addresses
The IP address and the corresponding mask must be set via the LHMI for each
available Ethernet interface in the IED. Each Ethernet interface has a default factory IP
address when the IED is delivered. This is not given when an additional Ethernet
interface is installed or an interface is replaced.
The default IP address for the IED front port is 10.1.150.3 and the corresponding
subnetwork mask is 255.255.255.0, which can be set via the local HMI path Main
menu/Configuration/Communication/TCP-IP configuration/1:ETHFRNT.
The default IP address for the IED rear port is 192.168.1.10 and the corresponding
subnetwork mask is 255.255.255.0, which can be set via the local HMI path Main
menu/Configuration/Communication/TCP-IP configuration/1:ETHLAN1 and
Rear OEM - port CD.
The front and rear port IP addresses cannot belong to the same subnet
or communication will fail. It is recommended to change the IP address
of the front port, if the front and rear port are set to the same subnet.
Setting up the PC or workstation for point-to-point access to IEDs front
port
A special cable is needed to connect two physical Ethernet interfaces together without
a hub, router, bridge or switch in between. The Tx and Rx signal wires must be crossed
in the cable to connect Tx with Rx on the other side and vice versa. These cables are
known as cross over cables. The maximum length should be about 2 m. The connector
type is RJ-45.
Section 4 1MRK 511 261-UUS A
Setting up a project
32 650 series ANSI
Engineering Manual