Technical data

Section 2 Engineering tool set
2.1 Introduction
The structure of a monitoring and control system for electrical substations has a
principle structure as shown in Figure 2. It contains a number of IEDs for the various
purposes.
For performance reasons, do not insert more than 150 IEDs of 650
series type in one PCM600 project. In PCM600 version 2.3, the
maximum number of IEDs is 60. Larger projects can be divided into
several PCM600 projects.
It can be subdivided in the three main parts:
Bay level IEDs
Station communication
Station level IEDs
IEC08000101.vsd
Bay level
Station level
Station
Communication
Station bus
bay
IED 1
bay
IED 2
bay
IED n-1
bay
IED n
NCC-GW
(station-IED2)
PCM600
(tool set)
HSI
(station-IED1)
IEC08000101 V1 EN
Figure 2: Principle structure of a monitoring and control system for a substation
All three parts require specific engineering and configuration. PCM600 is used to do
the complete engineering and configuration activities needed for bay level IEDs.
1MRK 511 261-UUS A Section 2
Engineering tool set
650 series ANSI 17
Engineering Manual