Technical data
To make it easier to recognize the signals for the active setting
group, the user-defined names are used.
2. Open the Communication Management Tool (CMT). Set the Signal Type to
Binary Input Object and choose the connection of the master for which the values
should be presented.
IEC11000424-1-en.vsd
IEC11000424 V1 EN
Figure 72: Communication Management tool
3. Select the signals and move them into the DNP signal list of the master. DNP
point zero and one of the Binary Input Objects are used for indicating the active
setting group in this case.
1MRK 511 261-UUS A Section 9
DNP3 communication engineering
650 series ANSI 117
Engineering Manual