Technical data
9.2  Adding setting groups
In order to show for a DNP master which setting group is used, the following
procedure can be performed.
In this example, only setting groups one and two are used. The DNP master will get
two binary inputs: the first is set if setting group one is used, the second is set if setting
group two is used.
1. Configure ACTVGRP (Basic IED functions) and SP16GGIO (Monitoring) with
the Application Configuration Tool (ACT).
IEC11000423-1-en.vsd
IEC11000423 V1 EN
Figure 71: Application configuration tool
Section 9 1MRK 511 261-UUS A
DNP3 communication engineering
116 650 series ANSI
Engineering Manual