Technical data

IEC08000418.vsd
IEC08000418 V1 EN
Figure 66: IEC 61850: Export IED file Options
7.4 Engineering of vertical and horizontal communication
in IET600
For IEC 61850 engineering a separate system configuration tool is needed to be used
with PCM600. In PCM600 Ver. 2.3 or earlier the recommended tool is CCT600. In
PCM600 Ver. 2.4 or later the recommended tool is IET600, which is also included in
the PCM600 Engineering Pro installation package.
Procedure for signal engineering for the station by using IET600:
1. Create a project in IET600.
2. Import the SCD file exported from PCM600.
All data sets, report control blocks and GOOSE control blocks
must be located at LD0/LLN0. Due to IED capability, there are
limitations regarding the maximum number of data sets, number of
entries in a data set and the number of report control blocks that
can be used.
3. Add and/or reconfigure default data sets. The 650 series pre-configured IED
includes a number of predefined data sets, but it is possible to add additional data
sets and/or reconfigure default data sets according to the requirements.
Note that reporting data sets shall only contain data intended to be
used by clients, for example for event handling.
4. Configure report control blocks for each data set used for vertical communication.
The 650 series pre-configured IED includes a number of predefined report control
Section 7 1MRK 511 261-UUS A
IEC 61850 communication engineering
106 650 series ANSI
Engineering Manual