Technical data

IEC09000627-1-en.vsd
IEC09000627 V1 EN
Figure 64: IEC 61850: SCL Export Options
5. Select Export Private Sections and click Export to export the private sections to
the SCD file. A progress window shows the ongoing export of the station.
7.3.2 Exporting ICD or CID files
Procedure to select the export type, when the IED is selected in the plant structure:
1. Right-click the IED in the plant structure and select Export to open the Export
window.
2. Select the type of file to export from the Save as type drop down list.
Configured IED Description (*.cid) for the IEC 61850 structure as needed
for the IED at runtime.
IED Capability Description (*.icd) for the IEC 61850 structure, see Figure
65.
IEC08000416.vsd
IEC08000416 V1 EN
Figure 65: IEC 61850: Export IED file type selection
3. The SCL Export Options window opens.
4. Select Export Private Sections, Export As SCL Template or Include Goose Sending
IEDs and click Export, see Figure 66. Note that the options in SCL Export Options
window according to
Figure 66 is only available when an ICD file is exported.
1MRK 511 261-UUS A Section 7
IEC 61850 communication engineering
650 series ANSI 105
Engineering Manual