Technical data

7.3 Exporting SCL files from PCM600
A pre-condition is that all IEDs in the project must be engineered in PCM600. The
hardware interface, for example the communication port, has to be selected and
configured. The used interface addresses have to be set according to protocol and
project definitions. The station communication port has to be activated in the IED, that
is to set the IEC61850-8-1Operation setting to Enabled.
7.3.1 Exporting SCD files
Procedure to export the SCD file from PCM600:
1. Select the station in the plant structure, see
Figure 63.
IEC08000415.vsd
Station
IEC08000415 V1 EN
Figure 63: IEC 61850: Export SCD step 1
2. Right-click the station and select Export ....
3. Select a location from the open standard Windows menu to store the file and name
it.
4. The SCL Export Options window opens, see
Figure 64.
Section 7 1MRK 511 261-UUS A
IEC 61850 communication engineering
104 650 series ANSI