Technical data
• Description of the substation part including the used logical nodes
• Description of the IEDs with their logical nodes
• Description of the communication network
• Description of the engineering process
For more details please refer to the IEC 61850 standards. In the following description it
is assumed that PCM600 together with IET600 is used as system configuration tool.
A short form of a typical sequence is shown in
Figure 62 when a complete station is
exported as a SCD file.
1. Export SCL files from PCM600. In the scenario in Figure 62 it is a SCD file.
Other SCL file types are possible to export.
2. Configure horizontal and vertical communication in the IET600 station
configuration tool.
3. Import SCL files to PCM600 project. In the scenario in
Figure 62 it is the updated
SCD file.
SCD file
do IED engineering
export SCD file
PCM600 (1)
create project
import SCD file
configure data sets
configure Report CBs
configure GOOSE CBs
export SCD file
IET600 (2)
import SCD file
link GOOSE input data
Write to IED
PCM600 (3)
SCD file
IED 1
IED nIED 2 IED n-1
IEC11000264.vsd
IEC11000264 V1 EN
Figure 62: IEC 61850: Signal engineering procedure flow
1MRK 511 261-UUS A Section 7
IEC 61850 communication engineering
650 series ANSI 103
Engineering Manual