Installation Guide

Installation GuideLightGrid Mesh Node 2.x Series
www.gecurrent.com
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the
General Electric Company and are used under license. Information provided is subject to change without
notice. All values are design or typical values when measured under laboratory conditions.
CTRL044 (Rev 11/30/21)
Questions
Email: lightgridsupport@gecurrent.com
Leave a Voicemail: 1-877-843-5590
Troubleshooting
Symptom Solution
The luminaire is not
turning ON.
Check that the pole has power. The relay inside the Controller is Normally Closed, so the
luminaire will always turn ON when the controller is rst plugged in.
I did not see the
dimming sequence in the
rst 60 seconds.
Unplug the controller, and try plugging it in again. If you still do not see the sequence, check
that the dimming wires of the xture (Grey & Violet) are properly connected to the dimming
wires of the ANSI socket. If you conrm the wiring is connected and the controller still does
not dim the luminaire, try another new controller.