Installation manual
8. Startup and Configuration 4-2010
2. With Output Volts selected on the Adjustments Menu screen, press the up or down arrow
button to adjust the voltage to the desired setting
3. The control allows an adjustment of 240 VAC ± 7% (17 VAC).
4. Press the BACK button to save the settings and return to the home screen.
8.7.2 To Calibrate the Display Meter
Use the following procedure:
1. Connect an accurate AC volt meter across L1 and L2 while the generator set is running.
2. Press the NEXT button to select the Display Cal field (screen not shown).
3. Press the up or down arrow to adjust the voltage reading on the screen until it matches the
meter reading.
4. Press the BACK button to save the settings and return to the home screen.
FIGURE 62. ADJUSTMENT MENU SCREEN