TABLE 22. PROPANE VAPOR PIPE CAPACITY - CUBIC FEET OF GAS PER HOUR
Nominal Iron Length of Pipe in Feet
Pipe Size
10 20 30 40 50 60 70 80 90 100 125 150
(Inches)
3/4 227 157 126
1 428 293 236 201 179 164 151 138 129 123 110
1 1/4 882 598 485 416 365 333 308 289 207 252 230 204
1 1/2 1323 920 743 624 567 570 472 434 409 390 346 315
2 2488 1732 1386 1197 1058 958 882 819 768 724 642 598
Maximum pipe capacity in cubic feet per hour of Propane vapor with a pressure drop of 0.5 inches (1.27 mm) WC
over the length
FIGURE 14. TYPICAL PROPANE VAPOR WITHDRAWL INSTALLATION
3.7.4.4 Converting From Natural Gas to Propane (Vapor Withdrawal)
The generator set leaves the factory set up for Natural gas.
For use with Propane, the generator must be converted by configuring the control for
Propane.
3.7.5 Testing the Fuel System for Leaks
WARNING: Fuel presents the hazard of explosion or fire which can result in severe
personal injury or death. Do not smoke or allow any flame, spark, pilot light,
arc-producing equipment, switch or other ignition sources around fuel or fuel
components.
Before operating the generator set, test the fuel system for leaks.
ยท Energize the fuel solenoid from a separate 12-volt DC source before testing the fuel
system
NOTE: Testing for gas leaks with a flame can cause a fire or explosion that can lead
to severe personal injury or death. Use approved methods only.
A029V088 (Issue 2) 31