Installation manual

3. Step-By-Step Outline of Installation 4-2010
FIGURE 5. GENERATOR SET CLEARANCES
3.3 Preparing the Site
Steps to preparing a proper/safe generator set site:
1. Create a level area
Add a layer of sand or pea gravel that is deep enough that the generator set will sit level.
2. Be sure that the area is at least 48 in by 34 in (1219 mm by 864 mm)
Sites on an incline require more area.
3. Be sure that the area is on firm ground
4. Remove any combustible material that would be under and around the generator set
3.4 Lifting and Moving the Generator Set
WARNING: The generator set is heavy. Dropping the generator set can cause severe
personal injury or death. Keep feet and hands clear when lifting the generator
set.
CAUTION: The generator is shipped with oil in the crankcase. Keep the generator set upright.
The generator set is heavy and must be handled with care.
· Use a fork lift to move the generator set and set it in place.
· The lifting eyes on the engine and alternator should not be used for lifting the entire
generator set.
· Alternatively, a one-person hand dolly designed to fit the generator set base is
available to move the generator and set it in place.
3.5 Staking the Generator Set in Place
WARNING: Pounding the stakes into electric, gas or telephone service lines can result in
severe personal injury or death. Observe the utility company markings and
discuss any other buried lines with the home owner.
16 A029V088 (Issue 2)