Specifications
9-2010 4. Maintenance
No. Description No. Description
1 Dipstick 2 Air Filter
3 Oil Filter 4 Oil Drain
5 Battery 6 Circuit Breaker
7 Control Switch
FIGURE 22. MAINTENANCE POINTS
4.6 Battery Maintenance
WARNING: Arcing at battery terminals or in light switches or other equipment, and
flames or sparks, can ignite battery gas causing severe personal
injury—Ventilate battery area before working on or near battery—Wear safety
glasses—Do not smoke—Switch work light ON or OFF away from
battery—Stop the generator set—Disconnect the negative (-) battery cable
first and reconnect it last.
WARNING: Before working on the generator set, move the Switch (S2) to the Stop
Position, disconnect the remote harness (P7) to disable the ATS mounted
charger, and remove the negative (-) battery cable from the battery to prevent
starting.
Refer to the Periodic Maintenance Table for scheduled battery maintenance, and follow the
battery manufacturer's instructions. Have the battery charger in the transfer switch replaced if
the battery keeps running down.