Product Card
cumminspower.com
©2014 Cummins Power Generation Inc. | DS342-CPGK-RevF (6/14)
Air
Standby
rating
Prime
rating
Combustion air, m
3
/min 2.30 2.30
Maximum air cleaner restriction, kPa 4
Exhaust
Exhaust
gas flow at set rated load, m
3
/min
Exhaust
gas temperature, °C 660 660
Maximum
exhaust back pressure, kPa 3.38
Standard set
-mounted radiator cooling
Ambient design, °C
50
Fan load, kW
m 0.95
Coolant capacity (with radiator), L
15
Cooling system air flow, m
3
/sec @ 12.7 mmH
2
O 0.78
Total hea
t rejection, Btu/min 882
Maximum cooling air flow static restriction
mm H
2
O
Weights
*
Open Enclosed
Unit dry weight
kgs 648 928
Unit wet weight kgs
799 1079
* Weights represent a set with standard features. See outline drawing for weights of other configurations.
Dimensions
Length (A) Width (B) Height (C)
Standard open set dimensions in mm
1667 930 1282
Enclosed set standard dimensions in mm
2082 987 1525
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.