Product Card
Open Enclosed
Dimensions
Air
Standby Rating Prime Rating
Combustion air, m
3
/min
12.72 12.30
Maximum air cleaner restriction, kPa 3.7-6.2
Exhaust
Exhaust gas flow at set rated load, m
3
/min
35.8 34.1
Exhaust gas temperature,
°
C
561 544
Maximum exhaust back pressure, kPa 10.2
Standard set-mounted radiator coolin
g
Ambient design,
°
C
50
Fan load, KW
m
6.8
Coolant capacity (with radiator), L 30.2
Cooling system air flow, m3/sec @ 12.7mmH2O 5.91
Total heat rejection, BTU/min 6516 5825
Width Height
Maximum cooling air flow static restriction mmH2O 8.12
Weights
*
Unit dry weight kgs 1544 2698
3900 1100 2072
Unit wet weight kgs 1670 3301
* Weights represent a set with standard features. See outline drawing for weights of other configurations
Length
Genset outlin
e
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
Standard open set dimensions 2656 1100 1658
Enclosed set standard dimensions
©2012 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS331-CPGK-RevD - 24/2/2012