Alternator data
Connection
1
Temp rise ºC Duty
2
Alternator Voltage
WYE 163 ESP UCI274E 190-208 & 380 - 416 V
WYE 150 ESP UCI274F 190-208 & 380 - 416 V
WYE 125 PRP UCI274E 190-208 & 380 - 416 V
WYE 105 PRP UCI274F 190-208 & 380 - 416 V
Ratings definitions
Emergency standby power
(ESP):
Limited-time running power
(LTP):
Prime power (PRP):
Base load (continuous)
power (COP):
Applicable for supplying power to
varying electrical load for the
duration of power interruption of a
reliable utility source. Emergency
Standby Power (ESP) is in
accordance with ISO 8528. Fuel
Stop power in accordance with
ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Applicable for supplying power
to a constant electrical load for
limited hours. Limited Time
Running Power (LTP) is in
accordance with ISO 8528.
Applicable for supplying power
to varying electrical load for
unlimited hours. Prime Power
(PRP) is in accordance with ISO
8528. Ten percent overload
capability is available in
accordance with ISO 3046,
AS 2789, DIN 6271 and BS
5514.
Applicable for supplying
power continuously to a
constant electrical load for
unlimited hours. Continuous
Power (COP) is in accordance
with ISO 8528, ISO 3046, AS
2789, DIN 6271 and BS 5514.
Formulas for calculating full load currents:
Three phase output Single phase output
Voltage
1000 x eFactorSinglePhas x kW
0.8 x 1.73 x Voltage
1000 x kW