Product Card

cumminspower.com
©2013 Cummins Power Generation Inc. | EMERD-5835a-EN (11/13)
Air
Standby
rating
Prime
rating
Combustion air, m
3
/min 8.95 8.35
Maximum air cleaner restriction, kPa 3.74
Exhaust
Exhaust
gas flow at set rated load, m
3
/min 31 29
Exhaust
gas temperature, °C 520 519
Maximum
exhaust back pressure, kPa 10.15
Standard set
-mounted radiator cooling
Ambient design, °C
50
Fan load, kW
m
9.8
Coolant capacity (with radiator), L
22.1
Cooling system air flow, m
3
/sec @ 12.7 mmH
2
O
3.77
Total heat rejection, Btu/min
4071 3867
Maximum cooling air
flow static restriction mm H
2
O 12.7
Weights
*
Open Enclosed
Unit dry weight
kgs
1635 2390
Unit wet weight kgs
1650 2400
* Weights represent a set with standard features. See outline drawing for weights of other configurations.
Dimensions
Length Width Height
Standard open set dimensions
2537 1090 1846
Standard enclosed set dimensions
3460 1090 2387
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.