Product Card
Open Enclosed
Dimensions
Air
Standby Rating Prime Rating
Combustion air, m
3
/min
131.00 120.00
Maximum air cleaner restriction, kPa 6
Exhaust
Exhaust gas flow at set rated load, m
3
/min
21.4 19.5
Exhaust gas temperature,
°
C
540 533
Maximum exhaust back pressure, kPa 10.5
Standard set-mounted radiator coolin
g
Ambient design,
°
C
54
Fan load, KW
m
5.60992
Coolant capacity (with radiator), L 19.75
Cooling system air flow, m3/sec @ 12.7mmH2O 3.44
Total heat rejection, BTU/min 9259 8419
Width Height
Maximum cooling air flow static restriction mmH2O 12.7
Weights
*
Unit dry weight kgs 1263 1963
3151 1142 1714
Unit wet weight kgs 1574 2274
* Weights represent a set with standard features. See outline drawing for weights of other configurations
Length
Genset outlin
e
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
Standard open set dimensions 2268 1094 1576
Enclosed set standard dimensions
©2012 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
Document no. DS381-CPGK-RevA - 24/2/2012