Specification Sheet
  cumminspower.com 
©2013 Cummins Power Generation Inc. | S-1639b (6/13) 
UL withstand and closing ratings 
The transfer switches listed below must be protected by circuit breakers or fuses. Referenced drawings include 
detailed listings of specific breakers or fuse types that must be used with the respective transfer switches. Consult 
with your distributor/dealer to obtain the necessary drawings. Withstand and Closing Ratings (WCR) are stated in 
symmetrical RMS amperes. 
Transfer 
switch 
ampere 
MCCB protection  Special circuit breaker protection 
WCR at volts 
max with 
specific 
manufacturers 
MCCBs 
Max MCCB 
rating 
Drawing 
reference 
With specific 
current limiting 
breakers (CLB) 
Max CLB 
rating  Drawing reference 
125  14,000 at 600 V  225 A  098-6885  200,000 @ 600 V  225 A  098-6918 
 225  30,000 at 600 V  400 A  098-6886  200,000 @ 600 V  400 A  098-6919 
400, 600  65,000 at 600 V  1200 A  098-6887  200,000 @ 600 V  1200 A  098-6920 
Fuse protection 
Transfer 
switch 
ampere 
WCR at volts 
max. with 
current limiting 
fuses  Max fuse, size and type  Drawing reference 
125  200,000 at 600 V  200 A Class, J, RK1, RK5, T  098-6885 
225  200,000 at 600 V  1200 A Class L or T, or 600 A class J, RK1, RK5  098-6886 
400, 600  200,000 at 600 V  1200 A Class L or T, or 600 A Class, J, RK1, RK5  098-6887 
Enclosures 
The transfer switch and control are wall-mounted in a key-locking enclosure. Wire bend space complies with 2011 NEC. 
Dimensions – transfer switch in UL type 1 enclosure 
Amp rating 
Height  Width 
Depth 
Weight  Outline drawing 
Door closed  Door open 
in  mm  in  mm  in  mm  in  mm  lb  kg   
125  27.0  686  20.5  521  12.0  305  31.5  800  82  37  0310-0544 
225  35.5  902  26.0  660  16.0  406  41.0  1042  165  75  0310-0414 
400, 600  54.0  1372  25.5  648  18.0  457  42.0  1067  225  102  0310-1307 
Dimensions – transfer switch in UL type 3R enclosure 
Amp rating 
Height  Width 
Depth 
Weight 
Cabinet 
type 
Outline 
drawing 
Door closed  Door open 
in  mm  in  mm  in  mm  in  mm  lb  kg     
125  34.0  864  26.5  673  12.5  318  36.5  927  125  57  3R  0310-0453 
225  42.5  1080  30.5  775  16.0  406  44.0  1118  215  97  3R  0310-0454 
400, 600  59.0  1499  27.5  699  16.5  419  41.5  1054  275  125 
3R  0310-1315 
4  0310-1316 
Dimensions for SE models– transfer switch in UL type 1 enclosure 
Amp rating 
Height  Width 
Depth 
Weight  Outline drawing 
Door closed  Door open 
in  mm  in  mm  in  mm  in  mm  lb  kg   
40, 70, 100, 
125 
45.8  1164  32.0  814  16.3  413.0  45.9  1165  300  136  0500-4721 
150, 200, 225, 
250 
73.6  1869  32.3  820  19.7  499.0  49.6  1259  500  227  0500-4606 
300, 400, 600  74.5  1892  34.4  873  20.1  510.4  50.9  1293  520  236  0500-4611 
Dimensions for SE models – transfer switch in UL type 3R or 12 enclosure 
Amp rating 
Height  Width 
Depth 
Weight  Outline drawing 
Door closed  Door open 
in  mm  in  mm  in  mm  in  mm  lb  kg   
40, 70, 100, 
125 
45.8  1164  32.0  814  16.3  413.0  45.9  1165  340  154  0500-4721 
150, 200, 225, 
250 
73.6  1869  32.3  820  19.7  499.0  49.6  1259  580  263  0500-4606 
300, 400, 600  74.5  1892  34.4  873  20.1  510.4  50.9  1293  600  272  0500-4611 