Commercial generator set
Standard Diesel
TM
Series
SD 7.5 60 Hz/6.0 50 Hz
Features and benefits
Weight, size and sound level
Smooth operation - focalized mounting system with
4-point vibration isolation
Glow plugs for reliable all-weather starting
Installation flexibility with remountable 90° exhaust
elbow, remountable DC control and multiple oil
fill/check points
Cross-flow radiator for increased cooling efficiency
Water resistant controls
Low harmonic distortion for SCR loads
Weight: 490 lb (223 kg), wet
Size:
- 60 Hz - Length 37.3 in (947 mm), width 21.0 in
(535 mm), height 23.9 in (607 mm)
- 50 Hz - Length 38.27 in (972 mm), width 21.0 in
(535 mm), height 23.9 in (607 mm)
Sound:
- 60 Hz - 76 dB(A) at 10 ft (3 m), 63 dB(A) at 50 ft
(15 m) before installation, full load
- 50 Hz - 75 dB(A) at 10 ft (3 m), 61 dB(A) at 50 ft
(15 m) before installation, full load
Models and ratings
Model Fan Hz
W
atts Voltage
A
mps PF Phase Circuit breaker
7.5HDKAL-1
Pusher 60 7500 120/240 62.5/31.3 1.0 1 2-pole, 35 A
7.5HDKAL-2
Suction 60 7500 120/240 62.5/31.3 1.0 1 2-pole, 35 A
7.5HDKAL-5010
#
Suction 60 7500 120/240 62.5/31.3 1.0 1 2-pole, 35 A
7.5HDKAL-3
Pusher 60 7500 120/240* 22.6 0.8 3 3-pole, kit
7.5HDKAL-5011
#
Pusher 60 7500 120/240* 22.6 0.8 3 3-pole, kit
7.5HDKAL-5
Pusher 60 7500 100/200 75/37.5 1.0 1 2-pole, 40 A
6HDKAL-7
Pusher 50 6000 115/230 52.1/26.1 1.0 1 2-pole, 30 A
6HDKAL-8
Suction 50 6000 115/230 52.1/26.1 1.0 1 2-pole, 30 A
6HDKAL-5009
#
Suction 50 6000 115/230 52.1/26.1 1.0 1 2-pole, 30 A
6HDKAL-9
Pusher 50 6000 115/230* 18.8 0.8 3 3-pole, kit
-
All 60 Hz models operate at 1800 r/min. All 50 Hz models operate at 1500 r/min.
-
Ratings apply up to 500 ft (152.4 m) altitude, 104° F (40° C) ambient** with No. 2 diesel fuel.
-
Maximum power decreases 3.5% for each 1000 ft (305 m) above 500 ft (153 m) and 1% for each 10° F (5.5° C) increase in ambient**
temperature above 85° F (29° C).
-
Ratings are at intermittent power output.
*
Three-phase models are 12-lead reconnectable for a broad range of voltage applications.
*
* Ambient is defined as the air temperature measured at the cooling air inlet to the set.
#
With export packaging.