6 Troubleshooting
6.1 Avoiding Generator Set Shutdowns
By regularly performing the following periodic maintenance and guidelines, you will
greatly reduce the chances of a generator set shutdown:
Maintain an appropriate oil level.
Keep battery connections clean and tight.
Do not overload the generator set.
Keep the air inlet and outlet openings clear.
Refer to the Maintenance section for more information.
6.2 Fault Code Introduction
Fault code information, together with warning and shutdown information, is provided
in this section to assist in locating and identifying the possible causes of faults in the
generator set system.
Refer also to the engine-specific operator manual, if it exists. The engine operator
manual contains additional information regarding the running and care of the
generator set as well as specific equipment instructions that may differ from the
standard generator set.
For any fault codes that occur but are not listed, contact your Cummins service
representative.
6.3 Engine Is Difficult to Start or Does Not Start
Possible Causes:
1. Battery voltage problem(s)
2. Fuel system issue(s)
3. Air intake restriction above specification
Diagnosis and Repair:
1. Battery voltage problem(s)
a. If battery voltage is low, interrupted, or open, check:
Battery connections
Unswitched battery supply circuit
Fuses
2. Fuel system issue(s)
a. Verify that the manual fuel shutoff valve is open.