Maintenance Items
After Every
24 Hours
of Run
Time
1
After Every
50 Hours
of Run
Time
12 Months or
After 250
Hours
2
2 Years or
After 500
Hours
2
Check operation of Emergency
Stop Button (where fitted): With
the generator set running, press
the Emergency Stop button.
Check all systems before
resetting the fault.
■
Replace air cleaner. ■
3
Check coolant lines and radiator
hoses for leaks, wear and
cracks: Visually check the
hoses. Replace worn or
damaged components.
■
Clean radiator core. ■
3
Check water pump for leaks.
Check weep holes for evidence
of leaks. Replace if leaking.
■
Verify that the coolant heater
has power and is running
(where fitted). Check for
evidence of leaks. Remove any
corrosion from fittings.
■
Check CCV heater (where
fitted). Check for evidence of
leaks. Remove any corrosion
from fittings.
■
Check alternator heater (where
fitted). Check general condition
and wiring connections.
■
Check battery heater (where
fitted). Check general condition
and wiring connections.
■
Check engine oil heater. Check
general condition and wiring
connections.
■
Check battery: Check
connections to verify that they
are secure.
■