Product Manual B

4. Operation - PowerCommand 1.1 3-2018
56 A051X877 (Issue 7)Copyright © 2018 Cummins Inc.
NOTICE
Open the generator set main line circuit breaker to prevent the transfer
switch from transferring building load to the generator set. The
generator set display will still show the RA series ATS transfer;
however, the switch will not transfer if the generator set breaker is
open.
1. In normal operation, the utility power is running to the transfer switch and
then to the building load, and the generator set is off.
2. Manually start the generator set via the standard control (HMI211)
mounted on the generator set.
FIGURE 27. MANUAL START SCREEN, STANDARD OPERATOR PANEL
3. The generator set starts.
4. If the ambient temperature is below 20 °F (6.7 °C), the generator set will
idle at 800 rpm for up to 2 minutes to allow sufficient turbo lubrication
after which the generator will ramp up to rated speed.
Idle time is linear from 2 minutes at -40 F (4 °C), or below to off at 20
°F (6.7 °C) or above.