Product Manual B
3. Control System 3-2018
50 A051X877 (Issue 7)Copyright © 2018 Cummins Inc.
Off Mode
When in Off mode, the control does not allow the generator set to start. If the
generator set is already running and the control is set to Off, it initiates a normal
shutdown sequence.
Manual Run Mode
When in Manual Run mode, the generator set starts and continues to run until the
control is put into the Off mode. While in Manual Run mode, the remote start signal
is ignored.
Auto Mode
When in Auto mode, the control allows the generator set to be started with a remote
start signal only.
When in Auto mode, the generator set can start at any time. When a remote start
signal is received, the genset starts after a time delay preheat (if programmed) and
time delay start (if programmed) is completed.
If the generator set is running in Auto mode and the Off button is pressed, the
control immediately stops the genset and the control transitions to the Off mode.
When all remote start signals are removed, the control performs a normal shutdown
sequence which may include a time delay stop.