Product Manual B

3. Control System 3-2018
32 A051X877 (Issue 7)Copyright © 2018 Cummins Inc.
Updating Exercise Frequency (3-Phase ATS)
NOTICE
Not applicable without an RA series transfer switch.
To update the exercise frequency and dates on the Clock/Exerciser Menu:
1. From any Information Menu, hold down the up and down arrows simultaneously
for two seconds. The Service Menu appears.
2. Access the Time Setup screen by selecting Clock Exerciser on the Genset
Service Menu.
3. Press the down key on the Time Setup screen to access the Daylight Saving
Adjust screen.
4. Select Adjust.
5. Press the down key on the Daylight Saving Adjust Start screen.
6. Select Adjust.
7. Press Exercise Schdr on the Daylight Saving Adjust End screen.
8. Press Adjust.
When updating these settings, the functions of the keys are as follows:
The horizontal right arrow key is used to select successive blocks for editing
settings on the screen.
Use the + or - keys to edit the following settings:
Schdr Enable: Enable or Disable
Exercise Schedule: Semi-Annual (every six months), Quarterly, Monthly,
Bi-Weekly (every two weeks) , or Weekly
Exercise Schedule: Day, Hours, Minutes, AM/PM
Press Save to save any changes. After saving, the Save button changes to the
Adjust button.