Product Manual A

6. Startup and Configuration PCC 2.37-2018
87A051X873 (Issue 10) Copyright © 2018 Cummins Inc.
6.5 Startup
WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the
starting battery cables, negative (–) cable first.
After verifying that the installation was completed correctly, start and test the
system. Make sure to connect the battery cables to the battery with the positive
(+) cable first.
Read through the operator manual and perform the maintenance and pre-start
checks as instructed.
The following information applies to C125 N6 and C150 N6 generator set
models only: Adaptive learn is an engine ECM function that allows the
generator set to "learn" its environment. There are small differences in the
performance of each engine and fuel system component, so the ECM uses
inputs from the engine sensors to adjust running conditions to operate more
consistently for each individual generator set.
After installation is complete and while testing the overall system function, you
must run the generator set with no active faults under load (that is, with the
transfer switch connected to maximum customer load available) until the engine
temperature reaches 65.5 °C (150 °F) to allow the adaptive learn function to
initialize.
The generator set is shipped from the factory with the proper level of engine oil
and coolant, but make sure to check each before starting the generator set.
Start and operate the generator set following all the instructions and
precautions in the operator manual.
Before leaving the site:
Ensure that the bonding bolts are installed into the service panels.
If the generator set is ready to be placed in service, put the generator set
in Auto mode to provide automatic standby power.
Make sure the circuit breakers are in the ON position.
NOTICE
Contact your local Cummins service representative if you encounter a fault
code.