Product Manual A

6. Startup and Configuration PCC 2.3 7-2018
84 A051X873 (Issue 10)Copyright © 2018 Cummins Inc.
Check Description
Batteries
Make sure that the batteries are charged, and that all connections are
clean, correct and tight (if applicable).
Auxiliary Powered
AC Supplies
Make sure that all auxiliary equipment is receiving power from the
customer’s supply.
Emergency Stop Make sure that the emergency stop button is fully operational.
Starting at the Operator Panel (Manual Run Mode)
NOTICE
Make sure that all Pre-start Checks are carried out before starting the
generator set. Do not attempt to start the generator set until it is safe to do
so. Warn all others in the vicinity of the generator set and connected load
equipment that the generator set is about to start.
STARTING IN MANUAL RUN MODE
1. Make sure the main circuit breaker is in the open position.
2. To start the generator set in the Manual Run mode:
a. Press the Manual button on the operator panel.
b. Press the Start button within ten seconds.
NOTICE
Failure to press the Start button within this time will result in the
generator set changing to the Off mode. Refer also to the Selecting
Manual Run Mode section.
NOTICE
If the mode change access code feature has been enabled, enter the
access code when prompted. See the Passwords and Mode Change
Access section.
3. The PowerCommand
®
control will initiate a starter cranking signal and will
perform an automatically sequenced manual start, under a complete engine
protection system combined with full monitoring capability. This will activate the
engine control system and the starting procedure. The starter will begin
cranking and, after a few seconds, the engine will start and the starter will
disconnect.
If the engine fails to start, the starter will disengage after a specified period of
time and the control will indicate a Fail to Start shutdown.