Product Manual A
6. Startup and Configuration PCC 2.3 7-2018
78 A051X873 (Issue 10)Copyright © 2018 Cummins Inc.
Tick General Items
Fuel lines are properly installed, supported, and protected against damage.
The fuel filters have been installed.
Approved flexible fuel line is installed between the main fuel supply and the generator
set’s fuel system near the generator set, to protect it against damage caused by
vibration, expansion, and contraction.
Strainer or fuel screen (100 to 200 mesh) is installed in the fuel supply line to protect
the fuel lift pump, day tank transfer pump, or float valve seat from fuel tank debris (if
applicable).
The fuel filter assembly shipped with the generator set is installed and operational (if
applicable).
Fuel supply shutoff valves are installed to prevent fuel flow in case of leaks.
No shutoff valves are installed on engine fuel return line (if applicable).
External fuel pumps are connected and operational at all times - generator set started
or shut down (if applicable).
Fuel tanks are filled with the correct grade / type of fuel (if applicable).
Fuel system is properly primed.
No fuel leaks are found in supply line or engine fuel system.
Gaseous Fuel System (if applicable)
Check fuel line and use equations to verify it has proper volume capability.
Check if fuel pressure is between 7-13 inches water column.
Check for any gas leaks.
If necessary, perform initial demand regulator adjustment procedure.
Make sure fuel pressure does not drop below 7 inches water column under full load.
Exhaust System
The breather tube routing is set up to blow the fumes away from the generator set (if
applicable)
Operators are thoroughly briefed on the dangers of carbon monoxide gas.
If the installation includes a heavy duty air cleaner, it has been installed.
Areas around generator set are well ventilated, with no possibility of exhaust fumes
entering building doors, windows, or intake fans.
Exhaust gases are piped safely outside and away from building.
The correct length of approved rigid pipe is connected to the generator set flexible
pipe using approved securing methods with no weight resting on engine exhaust
components. There are no bends in flex section.
Condensation drain is provided in lowest section of exhaust piping.