Product Manual A
5. Startup and Configuration PCC 1.17-2018
63A051X873 (Issue 10) Copyright © 2018 Cummins Inc.
NOTICE
These steps cannot be performed with the HMI211; they can only be
performed with the InPower service tool.
1. Connect to the PCC 1.1 or PCC 2.3 via InPower.
2. Navigate to the Adjustments->Features->Automatic Transfer Switch folder.
3. Select the Auto Mains Failure Enable parameter.
4. Double-click on Enabled in the Value field.
5. A pop-up will appear with available choices. Select Disabled.
6. Select Device->Save Adjustments from the top menu bar.
7. A pop-up will appear asking if the change is to be saved. Click the Save
button.
8. After a pop-up appears confirming that the change has been saved, disconnect
InPower from the PCC1302.