Product Manual A

4. Installation7-2018
39A051X873 (Issue 10) Copyright © 2018 Cummins Inc.
FIGURE 7. CIRCUIT BREAKER AC LOAD CONNECTIONS LOCATION (SYMBOLS
SHOWN AT BOTTOM)
6. Torque the circuit breaker terminals per specifications on the circuit breaker
label.
7. Torque the neutral lug to 31.1 Nm (275 in-lb).
8. Torque the equipment grounding lug to 13.8 Nm (120 in-lb).
9. Fill in the stub-up openings with an approved duct seal or mastic tape to keep
out insects and rodents.
10. Install the circuit breaker cover.