Product Manual A
3. Pre-Installation Considerations 7-2018
22 A051X873 (Issue 10)Copyright © 2018 Cummins Inc.
3.3 Required Items for Installation
Tools and materials are used for the installation of this generator set. These items
are identified in the following sections. Please refer to local codes and standards,
because they may affect the materials required.
Materials Required
NOTICE
Refer to local codes and standards, which may affect material requirements.
NOTICE
If a 100% rated breaker is used, 90 °C wire must be used for L1, L2, and L3
with the wire size determined by the 75 °C ampacity tables. Aluminum wire is
not allowed with 100% rated breakers.
NOTICE
A UL-listed grounding electrode terminal within its ratings and suitable for
the application must be installed and labeled “Grounding Electrode
Terminal”.
Electrical Materials:
NOTICE
Class 1 wiring methods must be used for connecting the generator set.
• Four code compliant AC power wires; L1, L2, N and Gnd (add another wire for
3-phase for a total of 5 AC wires)
• If an RA automatic transfer switch will be installed, refer to the RA Series
Transfer Switch Owner Manual.
• Wire sizes (DC control and power and AC sense only):
◦ DC control or AC sense wires under 1000 feet circuit length => 18-14
AWG of the insulation type below
◦ DC control or AC sense wires 1000-2000 feet circuit length => 16-14 AWG
of the insulation type below
• All AC and DC wires and cables must be rated 75 °C minimum, stranded
copper, and rated for wet locations.
◦ For wire sizes 14 AWG and larger, use insulation types: RHW, RHW-2,
THHW, THW, THW-2, THWN, THWN-2, XHHW, XHHW-2, USE-2, ZW-2
◦ For wire sizes 16 and 18 AWG, use insulation types: FFH-2, KFF-2, PAFF,
PFF, PGFF, PTFF, RFH-2, RFHH-2, RFHH-3, SFF-2, TFF, TFFN, ZFF
• Code compliant 20 A, 120 VAC, GFCI protected circuit for alternator heaters,
battery charger, coolant heater, oil heater, and/or battery heater (if equipped)