Product Manual B
2. Introduction 3-2018
18 A051X877 (Issue 7)Copyright © 2018 Cummins Inc.
TABLE 7. GENERATOR SET WET WEIGHT (POUNDS) (60 HZ, 1800 RPM)
Configuration C45 N6 C50 N6 C60 N6 C70 N6 C80 N6 C100 N6
Open 2180 2180 2431 2449 2587 2719
Weather 2359 2359 2610 2628 2766 2898
Sound Level 1 2455 2455 2706 2724 2862 2994
Sound Level 2 2485 2485 2736 2754 2892 3024
NOTICE
Weights are approximate and can be affected by selected options. Refer to
outline drawings for specific weight information.
TABLE 8. ALTERNATOR SPECIFICATIONS 60 HZ, 1800 RPM
Type C45 N6 C50 N6 C60 N6 C70 N6 C80 N6 C100 N6
Generator Brushless, 4-pole rotating field, single bearing
Power (kVA) 1 Phase 45 50 60 70 80 100
Power (kVA) 3 Phase 56.3 62.5 75 87.5 100 125
Rated Voltages (V)
120/240, 1 Ph
227/480, 3 Ph
347/600, 3 Ph
120/240, 3 Ph
120/208, 3 Ph
127/220, 3 Ph
F1PO (Reconnectable, Full Single Phase Output)
NOTICE
Maximum I
2
= 8%. Generator set load unbalance must not exceed 25%
between any phases.