6.2 InPower Service Tool
The InPower
TM
service tool can be used in troubleshooting to perform tests, verify
control inputs and outputs, and test protective functions. Refer to the InPower
User's Guide, provided with the InPower software for test procedures.
6.3 Checklist
Tick General Items
Generator set output is sufficient to handle maximum anticipated load.
At least 0.9 m (3 feet) of clearance (or greater for housing door) is provided around
the entire generator set for service and ventilation.
The generator set is located in an area not subject to flooding.
All operating personnel have read and are familiar with the generator set Operator
manual, all health and safety procedures, warnings, cautions, precautions, and the
other documentation supplied with the generator set.
All operators have been thoroughly briefed on preventative maintenance procedures.
All operators have read and understand all important safety instructions.
Any parts requiring software have been checked for the latest version. Contact the
service representative for more information.
Generator Set Position
The floor, roof, or earth on which the generator set rests is strong enough and will not
allow shifting or movement. Observe local codes on soil bearing capacity due to
freezing and thawing.
The generator set is properly supported and retained to an approved base.
The supporting base is large enough and is of non-combustible material, extending 15
cm (6 inches) all around the generator set.
Provisions have been made for site specific environmental operating conditions
(weather protection, proximity to coastline, dusty environments, etc.,)
Cooling Air Flow
Generator set air inlet is faced into the direction of strongest, prevailing winds.
Air inlet openings are unrestricted and are at least 1 to 1
1
/
2
times larger than air outlet
area.
Cooling air outlet is on downwind side of building (if not, a wind barrier is constructed).
Proper ducting material (sheet metal, canvas) is used between radiator and air outlet.
Diesel Fuel System (if applicable)
Fuel tanks meet or exceed all local, State, or National codes (if applicable).