Product Manual A
5. Startup and Configuration PCC 1.1 7-2018
62 A051X873 (Issue 10)Copyright © 2018 Cummins Inc.
The following information applies to C70 N6, C80 N6, and C100 N6 generator set
models only: Adaptive learn is an engine ECM function that allows the generator set
to "learn" its environment. There are small differences in the performance of each
engine and fuel system component, so the ECM uses inputs from the engine
sensors to adjust running conditions to operate more consistently for each individual
generator set. After installation is complete and while testing the overall system
function, the generator set must be run with no active faults under load (that is,
transfer switch connected to maximum customer load available) until the engine
temperature reaches 80 °C (175 °F) to allow the adaptive learn function to initialize.
The generator set is shipped from the factory with the proper level of engine oil and
coolant, but each should be checked before the generator set is started. Start and
operate the generator set following all the instructions and precautions in the
Operator Manual. Ensure that the bonding bolts are installed into the service panels
before leaving the site.
NOTICE
Before leaving the site, if the generator set is ready to be placed in service,
put the generator set in Auto mode to provide automatic standby power.
NOTICE
Contact your local Cummins service representative if you encounter a fault
code.
5.7 InPower Service Tool
The InPower
TM
service tool can be used in troubleshooting to perform tests, verify
control inputs and outputs, and test protective functions. Refer to the InPower
User's Guide, provided with the InPower software for test procedures.
5.8 Disabling the AMF Feature
NOTICE
This procedure must be performed by a qualified technician.
On single-phase units, the control is shipped with the Automatic Mains Failure
(AMF) feature enabled. This feature has logic to control the RA Automatic Transfer
Switch (ATS), including a 5-minute retransfer to utility delay. If you are not using an
RA ATS, you can eliminate the 5-minute retransfer to utility delay by disabling the
AMF feature using the instructions below.
NOTICE
This procedure is optional. If you do not disable the AMF feature, the
generator set will just run for an additional 5 minutes after the utility has
been restored.