Product Manual A

5. Startup and Configuration PCC 1.17-2018
61A051X873 (Issue 10) Copyright © 2018 Cummins Inc.
Tick Item
Wire sizes, wire types, insulation, conduits and connection methods all meet
applicable codes.
AC and DC wires are separated in their own conduit to prevent electrical induction.
All load, line and generator connections are well made and correct.
Generator Set Pre-Start
A safety check was performed just before starting.
The generator set engine is properly serviced with oil and coolant.
The battery is properly installed, serviced and charged.
The battery charger and engine coolant heater are connected and operational, if
applicable.
All generator set covers and safety shields are installed correctly.
The fuel supply is turned on.
All fuel shutoff valves are operational.
The date and time have been set in the generator set control.
The generator set operating mode has been selected.
5.6 Startup
WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the
starting battery cables, negative (–) cable first.
After verifying that the installation was completed correctly, start and test the
system. Make sure to connect the battery cables to the battery with the positive (+)
cable first.
Read through the Operator Manual and perform the maintenance and pre-start
checks as instructed.