Product Manual A

4. Installation7-2018
29A051X873 (Issue 10) Copyright © 2018 Cummins Inc.
WARNING
Gaseous fuels are flammable, explosive, and can cause severe personal
injury or death. Do not smoke if you smell gas, are near fuel tanks for fuel-
burning equipment, or are in an area sharing ventilation with such
equipment. Keep flames, sparks, pilot lights, electrical arcs, arc-producing
equipment and all other sources of ignition well away. Keep a type ABC fire
extinguisher handy.
In all fuel system installations, cleanliness is extremely important.
Make every effort to prevent fuel contamination from:
Moisture
Dirt
Excess thread sealant
Contaminants of any kind
Clean all fuel system components before installing.
Gaseous-fuel supply system design, materials, components, fabrication, assembly,
installation, testing, inspection, operation, and maintenance must comply with the
applicable codes. See NFPA Standards No. 37, 54, and 58. For seismic installation,
refer to the seismic label. Where seismic installation is required, there may be
specific anchorage requirements for the generator set and other installed
components.
Most codes require a manual shutoff valve ahead of a flexible fuel hose. The
manual valve should be of the indicating type. The generator set has electric
(battery-powered) shutoff valves included.
NOTICE
It is recommended that a shutoff valve be located near the generator set for
emergency shut off or servicing the generator set. Follow applicable codes.
Until the generator set is connected, cap the fuel line stub-up at the generator set to
prevent dirt from entering and gas from discharging if the gas supply shutoff valve is
opened accidentally.
To determine the required capacity, refer to the Fuel Line Selection section.
Natural Gas Fuel System
Requirements for a natural gas generator set are as follows:
Adequate fuel supply to operate correctly and run at full load
Pipeline quality gas
The length of the fuel supply pipe from the gas service entrance to the
generator set must be known to determine the correct fuel pipe size (refer to
the Fuel Line Selection charts)